Question.
Describe
the procedure for paralleling a 440-volt 3-phase AC generator with another
generator on the line.
Answer.
a- See that the generator circuit breaker and field switch
(if furnished) are open.
b.
See that the field rheostat handle is set to cut in all the field resistance.
c-
Make sure the voltage regulator control switch (if furnished) is turned to the
MANUAL position.
d. Make sure the manual voltage control is
set at the position that gives the lowest generator voltage.
e. Make sure that both prime mover and
electrical ends are examined for evidence of obstruction to moving parts
f. See that the oil reservoir for oil
ring lubricated bearings contains the right amount of oil as indicated by the
oil sight glass.
g. See that the unit is started and
brought up to speed in accordance with the instructions for the type prime
mover used.
Be
sure that the overspeed governor and trip and all
other safety devices are tested and functioning as required by these
instructions.
h. Check the lubrication of bearings, check oil and bearing temperatures.
i. See that the collector rings run true, that
all brushes ride freely in the brush holders, and that there is no chattering of
brushes.
j. For totally enclosed machines with coolers,
see that the water is flowing through the cooler, and see that there is no leakage of
water. Shut the heaters off (if
furnished).
k. Bring the generator up to approximately normal speed.
Close
the field switch and bring the voltage up to approximately normal and place the
voltage regulator in control.
1. Turn the voltmeter switch on the incoming
generator to indicate the generator voltage on the voltmeter.
m. Turn the voltmeter switch on the adjacent generator panel to
indicate the bus voltage.
n. Turn the voltage adjusting rheostat of the voltage regulator
until the incoming generator voltage is equal to the bus voltage
o. Compare the frequency of the incoming generator with that of the
bus and adjust to correspond with the bus frequency
p.
Turn the synchroscope switch to the ON position.
The synchro-scope will rotate in one direction or the
other.
Adjust
the speed of the generator by means of the governor motor control switch until
the synchroscope rotates very slowly in the clockwise
direction.
q. Be certain that the voltages of the bus and
the incoming generator are still equal, and close the generator circuit
breaker just before the synchroscope pointer passes
very slowly through the zero position (pointing vertically upwards).
When
synchronizing lamps are used instead of the synchroscope,
the midpoint of the dark period of the lamps corresponds to the vertical
position of the synchroscope pointer.
r. Turn the synchronizing switch to the OFF position.
s Adjust the generators so that the kilowatt
and the reactive KVA load is divided
evenly between them