Question
(a.)
Describe the protection incorporated in AC. electrical switchboards.
(b)
State with reasons what maintenance is required for switchboards and associated
equipment.
Metal-clad,
dead front switchboards are mandatory for ac systems.
Mechanical
strength and non flammable construction are obtained with the use of sheet
steel for the cubicles
A passage
way of at least 0.6m is left at the rear for access
Incorporation of ACB which is set to disconnect from the main bus in case
of faults, thus avoiding damage to MCR.
For HV
system it should be separately earthed again to prevent internal damages, due to
high earth fault current.
Various
interlocks are provided, example until the circuit is
dead the door cannot be opened.
Protection
devices are incorporated
Overload
relay / over current protection.
The
alternator breaker has an overcurrent trip, but a
major consideration is that the supply of power to the switchboard must be
maintained if possible.
The breaker
therefore is arranged to be tripped instantly only in the event of high overcurrent such as that associated with short circuit.
When overcurrent is not so high, a delay with inverse time
characteristic allows an interval before the breaker is opened.
During this
time the overload may be cleared.
Reverse
power protection
Alternators
intended for parallel operation are required to have a protective device which
will release the breaker and prevent motoring if a reversal of power occurs.
Under voltage protection.
Closure by mistake
of an alternator breaker when the machine is dead is prevented by an
under-voltage trip.
High low frequency trip.
The relay consist of electronic circuitory.
Once a high low frequency is detected by transducer [61.5/58.5] the breaker is
tripped.
Maintenance.
Indicator lamp test to be carried out at regular intervals to ensure all
in working order. Replace faulty lamps.
Visual examination of circuit breaker in main and emergency and
distribution boards.
Check
condition of main arcing, auxiliary contacts for signs of wear, misalignment
and overheating. If sevewr burning or pitting occurs
to the main contact they need to be filed and alignment of contact checked.
The arcing contact are normally subjected to burning and can be dressed
with smooth file. Emery paper should not be used as abrasive
particles gets embedded on the surface of the contact.
Arc chutes
are checked and cleaned and also alignment is checked.
All
internal wiring must be in good condition.
All connection to be checked for tightness.
All mechanical
linkages to be checked for any sign of wear
The racking
mechanism for removing breaker for servicing to localised position checked for
free movement.
The protective
devices like under voltage, low frequency and overload relays can be tested
either by simulation or practically reducing values below the set values.
Circuit breaker, time relay mechanism with oil dashpots must have the pots filled to correct level, with clean oil of type recommended by manufactures.