Question
Describe, with the aid of a
diagram, the operation of the following components of electrical equipment and
explain the purpose of EACH:
Under voltage protection;
Miniature
circuit breakers.
Its main function is to trip the
breaker when a severe voltage dip (around 50%) occurs. The U/V release on a
generator circuit-breaker also prevents it being closed when the generator
voltage is very low or absent.
An under voltage relay, which may
be magnetic or electronic, also provides back-up protection to short-circuit
protection.
This is achieved by lifting the
mechanical latch (which keeps the contacts closed) to allow the trip spring to
function which opens the breaker contacts.
The U/V release on a generator
circuit-breaker also prevents it being closed when the generator voltage
These are very small air circuit-breakers
fitted in moulded plastic cases.
They have current ratings of 5-100
A and generally thermal over-load and magnetic short-circuit protection. They
have a very limited braking capacity (about 3000 A) and are commonly used in
final distribution boards instead of fuses. The d.b.
is supplied via a fuse or MCCB with the required breaking capacity. MCBs must be replaced if faults develop — no maintenance is
possible