Requirements of efficient operation of refrigeration plant:-

 

(1) Evaporating temp. & press should be as high as possible, such that all heat transfer surfaces are kept clean, so that temp, difference across them is at its minimum. It is essential that evaporator surface are supplied with liq. Refrigrant at the correct temp and in correct condition.

(2) Condensing temperature should be as low as possible to keep the compressure deliver) pressure to a minimum. This means correct flow of water in the condenser and to keep air out of the system as being non-condensible. Air will raise the pressure by Dalton's law of partial pressure. Rule of thumb- A reduction in suction saturated pressure of 1°C would reduce the compressure capacity by approx 4% and similarly an increase in condensing saturation pressure of 1°C would reduce the capacity by a further 0.9%.

(3)Suction & Delivery valves must not leak. Correct operation of unloading device should be ensured. Valve leakage means reexpansion of gas from delivery to suction
pressure. And hence reduced pumping capacity.

(4)Clearance volume should be minimum otherwise volumetric efficiency will suffer.

(5)Temp, at inlet and outlet of each side of heat exchanger must be correct to ensure correct superheat (at evaporator) and sub-cooling temps.(at condenser)

(6)Refrigeration Capacity is directly proportional to the weight of refrigrant evaporated in the evaporator i.e. directly related to the weight of vapour pumped by the compressure. This is the sum of flash gas and liquid, so to keep the weight higher, flash gas should be minimum.

(7)Weight of refrigerant vapour pumped by a compressure depends directly on the temperature and hence pressure difference between the evaporator and the condenser, and this must be kept to a minimum.

 

(8)Density of gas at suction is higher at higher inlet temperature, so volumetric efficiency decreases by lowering the evaporation temperature.

Thermostatie Expansion Valve:-

The purpose of the thermostatie expansion valve is to control the degree of superheat at the exit of the evaporator coil such that only vapour enters the compressor suction, and no liquid carry over takes place into the compressor.

In one system, a bulb fitted at the exit of the evaporator coil along with a capillary tube filled with the liquid refrigrant used in the main system, is acting on top of the diaphragm and tending to open the valve when the degree of superheat increases. Whereas saturation pressure of the liquid refrigerant at the inlet of the evaporator acts on the lower side of the diaphragm as well as pressure exerted by the regulating spring acting on the lower side of the diaphragm tending to close the valve. The spring tension set by the regulating spindle, controls the degree of superheat, a typical value is 4°C to 6°C. At any constant operating condition, these forces are balanced.

In practice, to achieve the desired degree of superheat at the evaporator outlet, dry expansion evaporators require up to 20 percent of their cooling surfaces to be available to superheat the gas, the precise area varying with demand.

 

 

Equalising Line;-          

Where thermostatic expansion valves are required to operate with evaporators which are subject to large pressure drops, additional control is introduced by incorporating a pressure equalizing connection. In this pressure control type expansion valve, to maintain a fixed evaporator coil pressure, a equalizing line connection from outlet of evaporator acts inside a bellow upwards along with the spring force. The refrigerant filled bulb fitted at the exit of evaporator exerts pressure outside the bellow. Evaporator pressure reduction opens valve and pressure increase closes valve and when compressor stops, the rising pressure causes closure.

Evaporator Back Pressure Regulator Valve :-

The function of an evaporator or "back" pressure Regulator, is to prevent the pressure,, and therefore the saturation temperature of the refrigerated vapour in the evaporator from falling below a required minimum valve. The regulator is fitted between the evaporator and compressor.

In large installations, electronic temperature regulators are used to provide precise control of the air temperature in refrigerated cargo spaces or water temperature in a water chiller, by regulating the evaporator pressure and hence the temperature. It consists of Main Evaporating pressure regulating Back Pressure valve, Motorised Pilot valve, electronic controller and temperature sensor. The back pressure valve is opened and closed by the pilot valve, which regulates the pressure on top of the piston in the back pressure valve by means of a spring loaded diaphragm. The spring torce can be cnangea by the electric motor which is able to move a push rod up and down via a gear rack.

Operation :-

The temp, sensor measures the temp, of the cooled air leaving the evaporator. The registered temp, is continuously compared in the electronic controller with the preset reference temperature. As soon as a differential occurs between the measured value and set value, the controller sends the error signal with proportional plus integral control, electric impulses to the pilot valve motor, which moves the spindle of the pilot valve up or down.

If for example, the air temp, rises, the motor will move the

spindle up, the pressure on top of the piston of the main valve (Back Pressure valve) will increase, and the valve will move open slightly. As a result, the evaporator pressure and temperature will decrease, the gas flow or capacity will increase and the air temperature will fall again.

High Pressure Cut-out :-

In the event of high discharge pressure on the condenser side of the compressor due to loss of condenser cooling, air in the system and overcharge, the high pressure cut-out will cause the compressor to shut down.

The discharge press acts inside the bellow and opposed by spring setting. During normal operation switch arm is held by the switch arm catch and holds the electrical contact in place. Excessive pressure expands the bellow, switch arm catch goes down around its pivot and releases the switch arm so breaking the electrical contact, and causing the compressor to cut-out. The machine can not be restarted until the trouble has been remedied and switch re-set by hand.

 

INDEX ADV ENG                                                                                                NEXT